2.5mm wire for 4.2kW oven - MyBuilder (2024)

Electrical

Hi,

My electician has rewired the house and installed a 4.2kW oven (with a separate gas hob). The oven radial uses a 2.5mm wire with a 20 amp fuse, and the length of the wire from the consumer unit to the oven is about 4m. My builder has told me that the 2.5mm wire is unsafe, but my electrician insists it's okay because the oven has no hob. Can anyone confirm whether the 2.5mm wire is safe and compliant with the regulations?

..................

Thanks all, much appreciated.

neil999_43

5

5 Answers from MyBuilder Electricians

Best Answer

Electrical Safety Services

Scarning Member since 17 Oct 2011 696 jobs, 100% positive feedback

Builder normally equals BODGER! they are some of the biggest cowboys going and should not be touching or even commenting on electrical matters, as 99% of them are not electrically competent and have not undergone formal electrical training or hold relevant qualifications. Where as most Part P registered electricians do.

A 4200 watt (4.2Kw) oven at 230volts (4200 divided by 230 ) = 18.26 amps. A 2.5mm cable is capable of supplying around 23-25 amps depending on the method of installation, so is fine, safe and compliant on a 20amp circuit breaker. Its very clear that the builder is not an electrician and probably knows little or nothing about circuit design and calculating circuit current. If he did then he could have done this quick calculation and realised it was perfectly compliant with BS7671:2008.

Answered 10th Apr 2014

Liked182

Liked by the question poster

Dadson Electrical Limited

Hengoed Member since 14 May 2012 85 jobs, 98% positive feedback

Hello,
A quick calculation for your problem:
A 4.2kw oven =4200w
4200/240=17.5amps
A 2.5mm short length of cable without diversity applied for insulation etc is capable of 24amps

Therefore your 2.5mm cable over the short distance IS SUITABLE for the capacity of the oven.
The 20amp fuse is the correct size fuse.

But in doubt always consult your ovens manual on there MINIMUM specification for electrical conections.

I hope this helps you.
Leighton Haynes

Answered 10th Apr 2014

Liked by the question poster

kevin cassidy building contractors

Accrington Member since 16 Dec 2010 48 jobs, 100% positive feedback

You have not given the method of installation, they are as listed below. Your builder is only quoting from limited knowledge that generally cooker supplies are run in 6.0mm T+E and does not know how to calculate the requirements. It sounds like your electrician has taken the cable to its design limit if using method B or C which is acceptable.
2.5mm T+E
Installation method A (enclosed in conduit in a thermally insulating wall, etc)
current carrying capacity 18.5A (max MCB 16A)
Installation method B (enclosed in conduit on a wall or in trunking, etc)
current carrying capacity 23.0A (max MCB 20.0A)
Installation method C (clipped direct)
current carrying capacity 27.0 (max MCB 20.0A)

Answered 10th Apr 2014

Liked65

Liked by the question poster

DGM Electrical

Pontypridd Member since 11 Nov 2010 5 jobs, 100% positive feedback

Your electrician is right. The cooker will pull a max of 18amps and the cable is rated at around 24amps and protected by 20amp fuse so your good to go : )

Answered 10th Apr 2014

Like38

Liked by the question poster

Western ELectrical Installations

Caerphilly Member since 31 Mar 2010 247 jobs, 100% positive feedback

hi
4200w divided by 230v = 18.26 amps
from memory 2.5 t and e in normal conditions can carry apprx 27 amps
so :
cable is rated at 27amps
fuse is rated at 20amps
oven is rated at 18amps

the numbers look fine to me , however there are other things to consider.

i.e if the cable run travels through more than 400mm (depth) of thermal insulation the current carrying capacity of the cable has to be halved so the cable will become the weakest link in the chain.

are there other issues the builder has noticed that you have not posted?
best regards

Answered 10th Apr 2014

Like37

Liked by the question poster

2.5mm wire for 4.2kW oven - MyBuilder (2024)
Top Articles
Latest Posts
Article information

Author: Kerri Lueilwitz

Last Updated:

Views: 5377

Rating: 4.7 / 5 (67 voted)

Reviews: 82% of readers found this page helpful

Author information

Name: Kerri Lueilwitz

Birthday: 1992-10-31

Address: Suite 878 3699 Chantelle Roads, Colebury, NC 68599

Phone: +6111989609516

Job: Chief Farming Manager

Hobby: Mycology, Stone skipping, Dowsing, Whittling, Taxidermy, Sand art, Roller skating

Introduction: My name is Kerri Lueilwitz, I am a courageous, gentle, quaint, thankful, outstanding, brave, vast person who loves writing and wants to share my knowledge and understanding with you.